Current Transformers (CT)
From:   https://library.e.abb.com/public/30c62390ff6c461d8a9c342a3661b175/1VAP420006-FL_Std%20CT_VT%20Ratings_2019.pdf




IEEE Standard Ratings Standard multi-ratio current transformer taps Current and voltage transformers (CTs and VTs)
IEEE C57.13-2016, Table 11: Standard multi-ratio current transformer taps*
600:5 1200:5 2000:5 3000:5 4000:5 5000:5
Ratio Tap Ratio Tap Ratio Tap Ratio Tap Ratio Tap Ratio Tap
50:5X2-X3100:5X2-X3300:5X3-X4300:5X3-X4500:5X1-X2500:5X2-X3
100:5X1-X2200:5X1-X2400:5X1-X2500:5X4-X51000:5X3-X41000:5X4-X5
150:5X1-X3300:5X1-X3500:5X4-X5800:5X3-X51500:5X2-X31500:5X1-X2
200:5X4-X5400:5X4-X5800:5X2-X31000:5X1-X22000:5X1-X32000:5X3-X4
250:5X3-X4500:5X3-X41100:5X2-X41200:5X2-X32500:5X2-X42500:5X2-X4
300:5X2-X4600:5X2-X41200:5X1-X31500:5X2-X43000:5X1-X43000:5X3-X5
400:5X1-X4800:5X1-X41500:5X1-X42000:5X2-X53500:5X2-X53500:5X2-X5
450:5X3-X5900:5X3-X51600:5X2-X52200:5X1-X34000:5X1-X54000:5X1-X4
500:5X2-X51000:5X2-X52000:5X1-X52500:5X1-X45000:5X1-X5
600:5X1-X51200:5X1-X53000:5X1-X5
*Contact factory for customer specific ratio taps.
Standard accuracy class for IEEE C57.13-2016, Table 8: Standard accuracy class for metering service and corresponding limits of transformer correction factors*
Voltage Transformers Current Transformers
90% to 100% rated voltage 100% rated current+ 10% rated current 5% rated current
Accuracy
class
Min Max Min Max Min Max Min Max
0.15S--0.99851.0015--0.99851.0015
0.150.99851.00150.99851.0015--0.99701.0030
0.3S--0.99701.0030--0.99701.0030
0.30.99701.00300.99701.00300.99401.0060--
0.60.99401.00600.99401.00600.98801.0120--
1.20.98801.01200.98801.01200.97601.0240--
*Other accuracy requirements may be specified and should be included on the nameplate. +For current transformers, the 100% rated current limit also applies to the current corresponding to the continuous thermal current rating factor. Standard VT burdens at 60 Hz
Standard 5A secondary CT burden
IEEE C57.13-2016, Table 10: Standard 5A secondary CT burdens*
Burden designation Resistance (ohms) Inductance (millihenrys) Impedance (ohms) Volt- amperes Power factor
Metering burdens
E-0.04+0.040.00.041.01.0
E-0.2+0.200.00.205.01.0
B-0.10.090.1160.12.50.9
B-0.20.180.2320.25.00.9
B-0.50.450.5800.512.50.9
B-0.90.811.0400.922.50.9
B-1.81.622.0801.845.00.9
Relaying burdens
B-10.52.31.0250.5
B-21.04.62.0500.5
B-42.09.24.01000.5
B-84.018.58.02000.5

IEEE C57.13-2016, Table 19:
Standard VT burdens
at 60 Hz
Burden designation Secondary
volt-amperes
SecondaryBurden
power factor
W12.50.10
X25.00.70
M35.00.20
Y75.00.85
Z200.00.85
ZZ400.00.85